OED Home > Renewable Energy > Solar Energy > Systems: Glen Canyon NRA
Renewable Energy: Solar Energy: Systems:
Glen Canyon
National Recreation Area
Dangling Rope Marina
In 1992 Glen Canyon NRA spent over $140,000 to generate electricity for
Dangling Rope Marina at an average cost of $0.38/kilowatt-hour (kWh).
Diesel generators ran 24 hours per day and consumed 65,000 gallons of diesel fuel each year to provide electricity to the marina. Fuel was delivered by barge, 35 deliveries were made annually. The generators created significant air and noise pollution at Dangling Rope Marina and exposed Glen Canyon NRA to the potential risk of a diesel fuel spill in Lake Powell.
A partnership between NPS, the Utah Department of Natural Resources and a consortium of federal, state and private energy interests was created to provide financial resources, technical engineering assistance and project management expertise necessary to install a 115 kilowatt (kW) photovoltaic/propane-hybrid power system at Dangling Rope Marina which began operation in September of 1996. In December of 1998, the array was increased to 160 kW to accommodate increased energy needs due to expanded services and increased visitation.
Project Description
The PV/propane-hybrid system includes a 160 kW photovoltaic array, a
2.4 MWh battery bank, 250 kW inverter, and two 250 kW propane generators.
Installation of $22,000 of energy efficiency improvements including compact fluorescent lamps, and replacement of electric stoves, water heaters, furnaces and clothes dryers with propane-fueled appliances.
Financial participation in the initial $1.45 million project included the state of Utah ($250,000); U.S. Department of Energy -- Office of Utility Technology ($137,500), FEMP ($350,000), and Sandia National Laboratory ($175,000); PacifiCorp ($150,000); National Park Service ($343,000); ARAMARK ($40,000); and EPA ($75,000).
The $306,000 array expansion was funded by the state of Utah ($30,000); U.S. Department of Energy -- State Energy Program ($77,000); and ARAMARK ($199,000).
Results
Diesel fuel consumption to generate electricity from 1996 to 1998 has been reduced from an estimated 75,500 gallons per year to 37,000 gallons of diesel fuel-equivalent (53,600 gallons of propane).
Generator run-time was reduced from 8,760 hours per year to 2,500 hours. Shorter run-times mean less noise and lower levels of air pollution. Air emissions were reduced by an estimated 590 tons of CO2, 9,500 lbs. of NOX, and 3,000 lbs. of SOX annually.
The new 45 kW of array is estimated to save an additional 14,000 gallons of propane per year and reduce generator run time to 1,850 hours. Emissions will be reduced by an estimated 75 tons of CO2, and 2,340 lbs. of NOX annually.
Reliability and power service at Dangling Rope has markedly improved. PV system availability was 99.6% during the first year.
![]() |
![]() |
The battery bank. |
The inside of the 250 kilowatt inverter. |